518-449-7213
sales@audiovideocorp.com
Pro AV Catalog
Network Technologies Inc (NTI) - E-DI16DOR16-V2R
Request Quote
All Products
network-technologies-nti

Digital Input/Output Expander (Normally-Open Relay Contact Outputs), 1RU Rackmount

Model: E-DI16DOR16-V2R

  • Adds 16 digital inputs and 16 digital normally-open relay contact outputs to the E-2D/5D/16D. Interfaces with the E-2D/5D/16D via the RJ45 Sensor Port.
  • Digital inputs: 16 screw terminal pairs for connecting dry contact devices. One screw terminal pair for tachometer; 0 to 255 Hz. Accepts 26 to 16AWG wire. Potential free. Voltage range: 0 to +36VDC. Over-voltage surge protected.
  • Digital outputs: 16 screw terminal pairs for normally-open relay contact outputs. Accepts 26 to 16AWG wire. Potential free. Rated switching load: 0.5A @ 125VAC, 1A @ ±30VDC, 0.5A @ ±48VDC. Galvanic isolation: 1kV. Fused.
  • Supports CAT5/5e/6 cable up to 500 ft. (152.4 m)
  • Control via SNMP: Requires read-write community configuration. Digital inputs are fixed values (not writable) while output relays are writable. Locate OIDS using a MIB browser.
Compare
Project List
Product Info
Tech Specs
Related Products
Documents

Environment Monitoring System
Sensor Accessories Sensor accessories compatible with E-2D, E-5D and E-16D

Control via SNMP:

  • Requires read-write community configuration.
  • Digital inputs are fixed values (not writable) while output relays are writable.
  • Locate OIDS using a MIB browser.

Compatible with E-FSC Fiber Converter/Extender.

  • Use to extend sensor up to 1.2 miles (2 km) from the ENVIROMUX unit.

Knowledge Base

For more information, visit http://www.networktechinc.com/io-expander.html

  • Adds 16 digital inputs and 16 digital normally-open relay contact outputs to the E-2D/5D/16D. Interfaces with the E-2D/5D/16D via the RJ45 Sensor Port.
  • Digital inputs: 16 screw terminal pairs for connecting dry contact devices. One screw terminal pair for tachometer; 0 to 255 Hz. Accepts 26 to 16AWG wire. Potential free. Voltage range: 0 to +36VDC. Over-voltage surge protected.
  • Digital outputs: 16 screw terminal pairs for normally-open relay contact outputs. Accepts 26 to 16AWG wire. Potential free. Rated switching load: 0.5A @ 125VAC, 1A @ ±30VDC, 0.5A @ ±48VDC. Galvanic isolation: 1kV. Fused.
  • Supports CAT5/5e/6 cable up to 500 ft. (152.4 m)
  • Control via SNMP: Requires read-write community configuration. Digital inputs are fixed values (not writable) while output relays are writable. Locate OIDS using a MIB browser.
  • Includes 5V/3A power supply.
  • Current consumption: 75mA @ 5VDC
  • Compatible with E-2D/5D/16D.
  • Available options: desktop unit with wall mounting brackets, 1RU rackmount unit, dual side-by-side rackmount units in 1RU.
  • Compatible with E-FSC Fiber Converter/Extender. Use to extend sensor up to 1.2 miles (2 km) from the ENVIROMUX unit.
 
Request Quote